How to deal with the failure of self-priming fire pump

First, the causes and treatment methods of the self-priming fire pump of Shanghai Liangong Pumps are as follows:

1. Insufficient priming pump (or the gas in the pump is not exhausted). Treatment method: Refill the pump.

2, the pump steering is wrong. Processing method: check the direction of rotation.

3, pump speed is too low. Processing methods: check the speed, increase speed.

4, filter plug, bottom valve is not working. Processing methods: check the filter to eliminate debris.

5, suction height is too high, or vacuum suction tank. Treatment: reduce the suction height; check the suction tank pressure.

Second, the causes and treatment methods of the interruption of the self-priming fire pump discharge of Shanghai Liangong Pump are as follows:

1. Leakage of the suction line. Processing method: Check the connection of the suction pipe and the sealing of the stuffing box.

2, the suction side of the pump when the gas is not drained. Treatment: Re-injection pump required.

3, the suction side suddenly blocked by foreign matter. Processing methods: stop the pump to deal with foreign matter.

4, inhaled a lot of gas. Treatment methods: Check whether the inlet vortex, submerged depth is too shallow.

Third, the reasons for the large power consumption in the operation and processing methods are as follows:

1. The impeller and the wear ring, the impeller and the shell have friction. Treatment methods: Check and repair.

2. Four items in the same five. Processing method: Reduce the flow.

3, increase the liquid density. Treatment method: check the liquid density.

4, the packing pressure is too tight or dry friction. Treatment method: relax the packing, check the water seal tube.

5, bearing damage. Treatment: Check the repair or replacement of bearings.

6, high speed. Processing methods: check the driver and power supply.

7, the pump shaft bending. Processing methods: correct the pump shaft.

8, the axial force balance device failure. Treatment: Check the balance hole, return pipe is blocked.

9. Coupling misalignment or axial clearance is too small. Processing method: check alignment and adjust axial clearance.

Fourth, the pump can not start or start the cause of the load and processing methods are as follows:

1. The prime mover or the power supply is abnormal. Processing method: Check the power supply and prime mover.

2. The pump is stuck. Processing method: Check the coupling by hand and dismantle the check if necessary to eliminate part of the malfunction.

3, packing pressure is too tight. Treatment methods: relax the packing.

4. The discharge valve is not closed. Processing method: Close the discharge valve and restart.

5, the balance tube is not smooth. Treatment method: to clear the balance tube.